2.4 Control Terminals Circuit diagram for digital inputs (NPN current 16mA.) NPN Mode +24V PNP Mode +24V 1 4 1 4 2 2 3 2 2 3 1 1 The position of the control terminals DCM DCM 10V MI1 MI3 MI5 24V AVI RS-485 Terminal symbols and functions RA RB RC MI2 MI4 MI6 DCM ACM AFM Revision 2016/03, 6ELE, V1.14 2-9 Terminal Symbol Terminal Function Factory Settings (NPN mode) ON: Connect to DCM MI1 Forward-Stop command ON: Run in MI1 direction OFF: Stop acc. to Stop Method MI2 Reverse-Stop command ON: Run in MI2 direction OFF: Stop acc. to Stop Method MI3 Multi-function Input 3 Refer to Pr.04.05 to Pr.04.08 for programming the Multi-function Inputs. ON: the activation current is 5.5mA. OFF:
leakage current tolerance is 10µA. MI4 Multi-function Input 4 MI5 Multi-function Input 5 MI6 Multi-function Input 6 +24V DC Voltage Source +24VDC, 50mA used for PNP mode. DCM Digital Signal Common Common for digital inputs and used for NPN mode. RA Multi-function Relay output (N.O.) a Resistive Load: 5A(N.O.)/3A(N.C.) 240VAC 5A(N.O.)/3A(N.C.) 24VDC Inductive Load: 1.5A(N.O.)/0.5A(N.C.) 240VAC 1.5A(N.O.)/0.5A(N.C.) 24VDC Refer to Pr.03.00 for programming RB Multi-function Relay output (N.C.) b RC Multi-function Relay common +10V Potentiometer power supply +10VDC 3mA