hyundai — Руководство по эксплуатации Hyundai N500 — инвертор (EN)

N500 INSTRUCTION MANUAL Operation 1.2 Test Run This is the common connection example. Please refer to 4.1 Digital Operator, for the detailed use of the digital operator (NOP500). (1) To input the operation setting and the frequency setting from terminal control. [Arrangements] ① Please make sure that the connections are correctly secure. ② Turn the MCCB ON to supply power to the inverter. (The Yellow LED “POWER” on the digital operator should illuminate.) ③ Set terminal with the frequency setting selection[A01]. • Set A01 as indication code, press the ▶ key key once. • Set 01(TM) with the ▲ key or the ▼ key, press the STR key once to set the frequency setting for terminal.

(Indication code turns back to A001.) ④ Set terminal with the operation setting selection[A02]. • Set 01(TM) with the ▲ key or the ▼ key; press the STR key once to set the operation setting for terminal. • Set A002 as indication code, press the ▶ key once. (Indication code turns back to A002.) ⑤ Set monitor mode. When monitoring the output frequency, set indication code to d01. Or when monitoring the operating direction, set indication code to d04. ⑥ Input starting operation setting. • Turn ON between [FWD] and [CM1] of terminal. • Impress voltage between [ O ] and [ L ] of terminal to start operation. ⑦ Input ending operation setting.

1- 4 4 • Turn OFF between [ FWD ] and [ CM ] to stop slowly down.