Victron Energy · MultiPlus-II 8k, 10k and 15k · 2 стр.

Victron MultiPlus-II 8k, 10k, 15k Inverter/Charger Manual & Specs (Australia) (EN)

Оригинальное название: Victron MultiPlus-II 8k, 10k, 15k Inverter/Charger Manual & Specs (Australia)

Читать онлайн

Похожие инструкции

Содержание

Текст документа

Configuring, monitoring and control

The MultiPlus-II and ESS (Energy Storage System) functionality The MultiPlus-II is a multifunctional inverter/charger with all the features of the MultiPlus, plus an external current sensor option which extends the PowerControl and PowerAssist function to 100A. The MultiPlus-II is ideally suited for professional marine, yachting, vehicle and land based off-grid applications. It also has built-in anti-islanding functionality, and an increasingly long list of country approvals for ESS application. Several system configurations are possible. For more detailed information see the ESS Design and configuration manual.

PowerControl and PowerAssist - Boosting the capacity of a generator A maximum grid or generator current can be set. The MultiPlus-II will then take account of other AC loads and use whatever is extra for battery charging, thus preventing the generator from being overloaded (PowerControl function). PowerAssist takes the principle of PowerControl to a further dimension. Where peak power is so often required only for a limited period, the MultiPlus-II will compensate for insufficient generator power with power from the battery. When the load reduces, the spare power is used to recharge the battery. MultiPlus-II Solar energy:

AC power is available even during a grid failure The MultiPlus-II can be used in off grid as well as grid connected PV and other alternative energy systems. It is compatible with both solar charge controllers and grid-tie inverters. Two AC Outputs The main AC output features no-break functionality. Upon grid disconnection the MultiPlus-II takes over the load supply in under 20ms, ensuring uninterrupted operation of computers and electronics. The second AC output is active only when grid power is available on the AC input. Use this to connect non-critical loads that should not deplete battery, e.g., water heater or air conditioner.

Virtually unlimited power thanks to parallel and three-phase operation Three units of the same model can be configured for three-phase output. Configuring, monitoring and control Settings can be changed in a matter of minutes with the VictronConnect app or VEConfigure software (computer or laptop and MK3-USB interface needed) or via the VRM portal. Use the MultiPlus-II GX or add a Cerbo GX, Ekrano GX or Color Control GX to a MultiPlus-II for local or remote connectivity. Operational data can be stored and displayed on our VRM (Victron Remote Management) website, free of charge. When connected to the internet, systems can be accessed remotely, and settings can be changed.

Other monitoring and control options are available as well, like the VictronConnect app together with a VE.Bus Smart dongle, a Battery Monitor or the Digital Multi Control Panel. MultiPlus-II GX Standard application Grid parallel topology with MPPT solar charge controller MultiPlus-II 8k, 10k and 15k Inverter/chargers (Australia) 48/800\0 /110-100 230V, 48/10000/140-100 230V and 48/15000/200-100 230V

Стр. 1

Configuring, monitoring and control

Ekrano GX or Cerbo GX Provides intuitive system control and monitoring and enables access to our free remote monitoring website: the VRM Online Portal. Note: not required the MultiPlus-II GX unit, as these have an in-built GX device. VRM Portal Our free remote monitoring website (VRM) will display all system data in a comprehensive graphical format. System settings can be changed remotely via the portal. Alarms can be received by e-mail or push notification. VRM app Monitor and manage your Victron Energy system from your smart phone and tablet. Available for both iOS and Android.

Current Transformer To implement PowerControl and PowerAssist and to optimize self-consumption with external current sensing. Maximum current: 100 or 400A Interface MK3-USB Needed to configure the MultiPlus, Can be used with the VictronConnect app or VE.Configure software. The interface connects to the MultiPlus via an RJ45 UTP cable and plugs into a USB port. Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands E-mail:

sales@victronenergy.com | www.victronenergy.com MultiPlus-II 48/8000/110-100 48/10000/140-100 48/15000/200-100 230V 230V 230V PowerControl & PowerAssist Yes Transfer switch 100 A Maximum AC input current 100 A INVERTER DC Input voltage range 38 – 66 V AC Output voltage 230 V ± 2% AC output frequency 50 Hz ± 0,1% (1) AC output current 29 A 36 A 54 A Cont. output power at 25°C (3) 8000 VA 10000 VA 15000 VA Cont. output power at 25°C 6400 W 8000 W 12000 W Cont. output power at 40°C 5500 W 7000 W 10000 W Cont.

output power at 65°C 4000 W 6000 W 7000 W Peak power 15000 W 18000 W 27000 W Maximum output fault current 80 A 100 A 150 A Maximum output overcurrent protection 135 A 143 A 165 A AC out 1 Maximum output overcurrent protection 50A AC out 2 Overvoltage category for all ports OVC III Active anti-islanding method Frequency Shift method Maximum battery discharge current 188 A 235 A 350 A Maximum efficiency 95% 96% 95% Zero load power 29 W 38 W 55 W Zero load power in AES mode 19 W 27 W 39 W Zero load power in Search mode 3 W 4 W 6 W Inverter topology Isolated CHARGER AC Input voltage range 230V ± 10% AC Input frequency range 45 – 65 Hz Maximum AC Input current while 27A 32A 48A charging Charge voltages Absorption:

57.6 V, Float: 55.2V, Storage: 52.8V Max. battery charge current (4) 110 A 140 A 200 A Battery temperature sensor Optional. Order number:

ASS000001000 Compatible battery chemistries Lead-acid, Lithium and others (5) GENERAL Auxiliary AC output Yes (50A) AC output-1 current with Power assist 129 A 136 A 154 A AC output-2 current with Power assist 50 A External AC current sensor (optional) 100 A Programmable relay (6) Yes Protection (2) a-g VE.Bus communication port Yes General-purpose communication port Yes, 2x Remote on/off terminal Yes Operating temperature range -20 to +65°C (fan-assisted cooling) Rated short-time withstand current 6 kA (Icw) Environmental category Indoor conditional Pollution degree 2 Humidity (non-condensing) max 95% Maximum altitude 2000m Country of manufacture India ENCLOSURE Material & Colour Steel, blue RAL 5012 Protection category IP21 Battery-connection M8 bolts AC connections Screw terminals for wire up to 13mm² (6 AWG) Weight 42 kg 49 kg 80 kg Dimensions hxwxd (mm) 642 x 363 x 206 677 x 363 x 206 810 x 405 x 217 STANDARDS EN-IEC 60335-1, EN-IEC 60335-2-29, Safety EN-IEC 62109-1, EN-IEC 62109-2 AS IEC 62477.1:2022, AS/NZS 4777.2:

2020+A1+A2 Emission, Immunity EN 55014-1, EN 55014-2 EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3 1) Can be adjusted to 60Hz 2) Protection key: 3) Non-linear load, crest factor 3:1 a) output short circuit 4) Up to 25°C ambient b) overload 5) Other chemistries are possible as well, providing the c) battery voltage too high charger is configured confirm the battery manufacturer’s d) battery voltage too low specifications. e) temperature too high 6) Programmable relay which can be set for general alarm, f) 230Vac on inverter output DC under voltage or genset start/stop function. AC rating: g) input voltage ripple too high 230V / 4A, DC rating:

4A up to 35VDC and 1A up to 60VDC

Стр. 2