8 Questions Answers Details described in: How can I show a decimal point in a Data Display object (i.e. the scale setting in NS)? Enter a computational expression in [Expression] under [Behavior] in the [Properties] tab page. 2-3-9 Decimal Display of Integer-type Values How can I deactivate the popup that comes up when selecting an already raised alarm event? Uncheck the “Popup” checkbox of the User Alarm. 2-3-10 Alarm Objects Cannot distinguish the raised alarms from the reset alarms by default. How can I do it? Add “Status” to [ColumnTitles], [ColumnOrder], and [ColumnWidths] under [Appearance] in the [Properties] tab page.
2-3-10 Alarm Objects How can I set a macro equivalent to the one that is run in NS upon loading a project? In the Global Events menu, set a subroutine that is created for “ProjectInitialzation”, the condition to start up the project. 2-4-1 How To Specify Subroutines (Macro) in the System Settings How can I set a macro equivalent to the one that is run in NS when an alarm event is raised or reset? Set a subroutine that is created for an event and action of each user alarm. 2-4-1 How To Specify Subroutines (Macro) in the System Settings How can I set a macro equivalent to the one that is run in NS when a value is changed?
In the Global Events menu, set a subroutine that is created for “Condition”, the condition for a value to change. 2-4-1 How To Specify Subroutines (Macro) in the System Settings Is it possible to connect an NA with a CJ-series CPU? You can connect the target CPU by registering it as an external device. At this point, only Ethernet connection is supported (i.e. the NA units do not support serial connection). 2-4-2 Connecting with the CJ-series CPU Is it possible to switch the screen from the PLC? Is it also possible to report the current screen from NA to PLC?
On the NJ, specify a String-type variable and assign it to “ HMI CurrentPage”, a system _ _ variable that specifies the current screen. You can change the screen by entering the name of the destination screen in the variable assigned to the system variable. If the address values are directly linked with the page numbers as in NS series, you must write Visual Basic. 2-4-3 How To Switch the Screen by the PLC Variables