Delta · PMT · 14 стр.
PMT-24V200W1AX (August 2013, Rev. 00) (EN)
Оригинальное название: PMT-24V200W1AX (August 2013, Rev. 00)
Похожие инструкции
Содержание
Текст документа
Model Numbering
TECHNICAL DATASHEET PMT Panel Mount Power Supply 24V 200W 1 Phase / PMT-24V200W1A PMT Highlights & Features AC input voltage selectable by switch Full Aluminium casing for light weight and corrosion resistant handling Convection cooling Cold start -20°C at 100% load (200W) Low leakage current High MTBF > 700,000 hrs. as per Telcordia SR-332 Short Circuit / Overvoltage / Overcurrent / Over Temperature Protections Safety Standards CB Certified for worldwide use Model Number: PMT-24V200W1A Unit Weight : 0.63 kg Dimensions (L x W x D):
215 x 115 x 50 mm General Description The new PMT series of panel mount power supplies is the latest offering from one of the world’s largest power supply manufacturers and solution providers - Delta. The product offers a wide operating temperature range from -10°C to +60°C and can withstand shock and vibration requirements (in accordance to IEC 60068-2-27 and IEC 60068-2-6 respectively). In addition to features like overvoltage and overload protections, Delta’s PMT series of panel mount power supplies is unlike many other brands in the same price level. The PMT series is designed for cost competitive markets without compromising the quality of the components and product specifications.
The series of products has an expected life time of 10 years. This versatile series has two different connector options (Terminal Block and Front Face) and can also be converted into L Frame (PML) type of power supplies to satisfy different application needs. Model Information PMT Panel Mount Power Supply Model Numbering *Options 1 All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (August 2013, Rev.
00) Model Number Input Voltage Range Output Voltage Output Current PMT-24V200W1A☐☐ 90-132Vac, 180-264Vac (Selectable by Switch) 24Vdc 8.80A CC Code PM □ – 24V 200W 1 A □ □ Panel Mount Product Type T – Enclosed L – L Frame* Output Voltage Output Power Single Phase No PFC Connector Type M – Terminal Block N – Front Face* Blank – Without connector cover A – With connector cover
Mechanical
TECHNICAL DATASHEET PMT Panel Mount Power Supply 24V 200W 1 Phase / PMT-24V200W1A Specifications Input Ratings / Characteristics Output Ratings / Characteristics Mechanical 2 All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (August 2013, Rev.
00) Nominal Input Voltage 100-120Vac, 200-240Vac (Selectable by Switch) Input Voltage Range 90-132Vac, 180-264Vac (Selectable by Switch) Nominal Input Frequency 50-60Hz Input Frequency Range 47-63Hz Input Current Efficiency at 100% Load > 88.5% @ 230Vac Max Inrush Current Leakage Current Nominal Output Voltage 24Vdc Output Voltage Tolerance ± 1% (initial set point tolerance from factory) Output Voltage Adjustment Range 21.6-26.4Vdc Output Current 8.80A Output Power 211.2W Line Regulation ± 0.5% typ. (@ 100-132Vac & 200-264Vac) Load Regulation ± 0.5% typ. (@ 100-132Vac & 200-264Vac ) PARD (20MHz) Rise Time 30ms typ. @ 115Vac, 20ms typ. @ 230Vac (100% load) Start-up Time 1000ms typ.
@ 115Vac & 230Vac (100% load) Hold-up Time 20ms typ. @ 115Vac, 24ms typ. @ 230Vac Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 5% @ 0-100% load Start-up with Capacitive Loads 8,000µF Max Case Chassis Aluminium Case Cover Aluminium Dimensions (L x W x D) 215 x 115 x 50 mm Unit Weight 0.63 kg Indicator Green LED (DC OK) Cooling System Convection Terminal PM☐-24V200W1AM☐ M3.5 x 9 Pins (Rated 300V/15A) PM☐-24V200W1AN☐ M3.5 x 9 Pins (Rated 300V/20A) Wire AWG 22-12
Safety Standards / Directives
TECHNICAL DATASHEET PMT Panel Mount Power Supply 24V 200W 1 Phase / PMT-24V200W1A Environment Protections *PE: Primary Earth Reliability Data Safety Standards / Directives 3 All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (August 2013, Rev. 00) Surrounding Air Temperature Operating -10°C to +60°C (Cold start at -20°C) Storage -25°C to +85°C Power De-rating > 40°C de-rate power by 2.5% / °C Operating Humidity 10-95% RH (Non-Condensing) Operating Altitude 5,000 Meters Shock Test (Non-Operating) IEC 60068-2-27, Half Sine: 50G for a duration of 11ms, 3 times for each 3 directions Vibration (Non-Operating) IEC 60068-2-6, Random:
5Hz to 500Hz @ 2.09Grms, 20 min per axis for all X, Y, Z direction Pollution Degree 2 Overvoltage 27.6-32.4V, Hicc-up Mode, Non-Latching (Auto-Recovery) Overload / Overcurrent 105-150%, Hicc-up Mode, Non-Latching (Auto-Recovery) Over Temperature Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed) Short Circuit Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed) Protection Against Shock Class I with PE* connection MTBF > 700,000 hrs. as per Telcordia SR-332 I/P: 100Vac, O/P: 100% load, Ta: 35°C Expected Cap Life Time 10 years (115Vac & 230Vac, 50% load @ 40°C) Electrical Safety UL/cUL recognized to UL 60950-1 and CSA C22.2 No.
60950-1, CB scheme to IEC 60950-1 Material and Parts RoHS Directive 2011/65/EU Compliant Galvanic Isolation Input to Output 3.0KVac Input to Ground 1.5KVac Output to Ground 0.5KVac
Block Diagram
TECHNICAL DATASHEET PMT Panel Mount Power Supply 24V 200W 1 Phase / PMT-24V200W1A EMC *Fulfills tested conditions 1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common mode (Line to earth) 3) Symmetrical: Differential mode (Line to line) Block Diagram 4 All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (August 2013, Rev. 00) EMC / Emissions* CISPR 22, EN 55022, FCC Title 47: Class A (With Delta EMI filter P/N: 10DKAW5) Immunity to* EN 55024 Electrostatic Discharge IEC 61000-4-2 Level 4 Criteria A1) Air Discharge: 15kV Contact Discharge:
8kV Radiated Field IEC 61000-4-3 Level 2 Criteria A1) 80MHz-1GHz, 3V/M with 1kHz tone / 80% modulation Electrical Fast Transient / Burst IEC 61000-4-4 Level 3 Criteria A1) 2kV Surge IEC 61000-4-5 Level 3 Criteria A1) Common Mode2): 2kV Differential Mode3): 1kV Conducted IEC 61000-4-6 Level 3 Criteria A1) 150kHz-80MHz, 3Vrms Power Frequency Magnetic Fields IEC 61000-4-8 Criteria A1) 10A/Meter Voltage Dips IEC 61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable Low Energy Pulse Test (Ring Wave) IEC61000-4-12 Level 3 Criteria A1) Common Mode2): 2kV Differential Mode3): 1kV