Table A.1 (continued) 59 Parameter name and designation Modbus address Modbus function Write / Read Hash- code Format, data size Range of values and indication Factory settings 3 (—.—) 4 (–.——) Type of work after reaching setpoint SPM 0×000A 0×06, 0×10 / 0×03 0×69B2 Word (2 bytes) 0 – Continue counting without resetting (CONT) Continue counting without resetting 1 – Stop the counting until a "RESET" signal (STOP) 2 – Reset the counter and continue counting (RESET) Type of work to "Reset" signal rSt 0×000B 0×06, 0×10 / 0×03 0×4C9A Word (2 bytes) 0 – Reset the counter (1) Reset the counter 1 – Reset the counter and disable output signals (2) 2 – Reset the counter and wait for signal "Start" (3) 3 – Reset the counter and wait for signal "Stop" (4)