SAMI GS 4.2 Mounting Note! Do not handle or lift the drive using the front cover. Use the bottom part for handling. Cooling air outlet d (see table below) To ensure safe installation, check that the surface mounting is flat. Mark the fixing points of SAMI GS on the wall using the template printed on the protective cardboard package as a guide. The maximum size of the fixing screws is 6 mm (15/64") for ACS 501-004- 3...006-3 and ACS 501-005-5...009-5 units and 8 mm (5/16") for 009-3...060-3 and 016-5...070- 5 units. 50 mm 50 mm Fix the screws to the marked positions. Attach the unit by the fixing notches and tighten the screws. Note!
If multiple units are installed adjacent or above each other, the following minimum distances apply: - units side by side, clearance 100 mm- units above each other, clearance 300 mm Cooling air inlet 50 mm Figure 4-3. Space requirement for adequate cooling. 14 SAMI GS Type d/[mm] ACS 501-004...011-3 ACS 501-005...016-5 ACS 501-016...060-3 ACS 501-020...070-5 150 150 250 250