SAMI G S 34 MAIN GROUP PARAMETER DEFAULT CUSTOMER SETTING 20 Drive 21 Acceler/Deceler 1 Acc/Dec Ramp Shape Linear 2 Acceler Time 1 3 s 3 Deceler Time 1 3 s 4 Acceler Time 2 60 s 5 Deceler Time 2 60 s 6 Acceler Ref2 Time 60 s 7 Deceler Ref2 Time 60 s 22 Freq/Cur Limits 1 Minimum Frequency 0 Hz 2 Maximum Frequency 50 Hz 3 Output Current 1.5*I [A] N 4 Maximum Freq.
range 120 Hz 23 Crit Frequencies 1 Crit Freq Select Off 2 Crit Freq1 Low 0 Hz 3 Crit Freq1 High 0 Hz 4 Crit Freq2 Low 0 Hz 5 Crit Freq2 High 0 Hz 6 Crit Freq3 Low 0 Hz 7 Crit Freq3 High 0 Hz 8 Crit Freq4 Low 0 Hz 9 Crit Freq4 High 0 Hz 10 Crit Freq5 Low 0 Hz 11 Crit Freq5 High 0 Hz 24 Const Frequencies 1 Const Frequency 1 5 Hz 2 Const Frequency 2 10 Hz 3 Const Frequency 3 4 Const Frequency 4 15 Hz 20 Hz 5 Const Frequency 5 25 Hz 6 Const Frequency 6 40 Hz 7 Const Frequency 7 50 Hz 25 PI-Controller (Parameters available only if PI- Control macro has been selected) 1 PI-Cont Gain 100 % 2 PI-Cont I-Time 60 s 3 PI-Cont Min Lim 25 Hz 4 PI-Cont Max Lim 50 Hz 5 Error Value Inv No 6 Actual Value Sel Act1 7 Actual 1 Input No 8 Actual 2 Input No 9 Actual1 Min Scale 0 10 Actual1 Max Scale 0 11 Actual2 Min Scale 0 12 Actual2 Max Scale 0 26 Start/Stop 1 Start Function Ramp 2 Torque Boost Cur 1.5*I [A] N 3 Stop Function Coast 4 Brake Chopper No 5 DC-Holding Off 6 DC-Hold Voltage 0.01*U [V] 7 DC-Brake Voltage 8 DC-Brake Time N 0.01*U [V] N 0 s