Siemens — Motor starter protector/circuit breaker + contactor

© Siemens AG 2009 Motor starter protector/circuit breaker + contactor CLASS 10, type of coordination 2, short-circuit breaking capacity I q = 50 kA 400 V AC 1) Guide value for 4-pole standard motors for 400 V AC, 50 Hz. Selection de- pends on the concrete startup and rated data of the protected motor. 2) Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible. 3) Alternatively 3VL27 16-2SP33 also possible. 4) Alternatively 3VL37 25-2SP36 also possible. 5) Alternatively 3VL47 31-2SP36 also possible.

Selection tables 400 V AC 11 Standard induction motor 4-pole at 400 V AC1) Setting range Overload release Motor starter pro- tector/circuit breaker Motor starter protec- tor/circuit breaker Contactor2) Size Short-circuit breaking capacity Iq Standard out- put P Motor current (guide value) I kW A A Order No. Order No. kA 0.06 0.2 0.14 ... 0.20 3RV10 11-0BA10 3RT10 15-1AP01 S00/S00 50 0.06 0.2 0.18 ... 0.25 3RV10 11-0CA10 3RT10 15-1AP01 S00/S00 50 0.09 0.3 0.22 ... 0.32 3RV10 11-0DA10 3RT10 15-1AP01 S00/S00 50 0.09 0.3 0.28 ... 0.40 3RV10 11-0EA10 3RT10 15-1AP01 S00/S00 50 0.12 0.4 0.35 ... 0.50 3RV10 11-0FA10 3RT10 15-1AP01 S00/S00 50 0.18 0.6 0.45 ...

0.63 3RV10 11-0GA10 3RT10 15-1AP01 S00/S00 50 0.25 0.85 0.55 ... 0.80 3RV10 11-0HA10 3RT10 15-1AP01 S00/S00 50 0.25 0.85 0.70 ... 1.00 3RV10 11-0JA10 3RT10 15-1AP01 S00/S00 50 0.37 1.1 0.90 ... 1.25 3RV10 11-0KA10 3RT10 15-1AP01 S00/S00 50 0.55 1.5 1.10 ... 1.60 3RV10 11-1AA10 3RT10 15-1AP01 S00/S00 50 0.75 1.9 1.40 ... 2.00 3RV10 11-1BA10 3RT10 15-1AP01 S00/S00 50 0.75 1.9 1.80 ... 2.50 3RV10 21-1CA10 3RT10 24-1AP00 S0/S0 50 1.1 2.7 2.20 ... 3.20 3RV10 21-1DA10 3RT10 24-1AP00 S0/S0 50 1.5 3.6 2.80 ... 4.00 3RV10 21-1EA10 3RT10 24-1AP00 S0/S0 50 1.5 3.6 3.50 ... 5.00 3RV10 21-1FA10 3RT10 24-1AP00 S0/S0 50 2.2 5.0 4.50 ... 6.30 3RV10 21-1GA10 3RT10 24-1AP00 S0/S0 50 3 6.5 5.50 ...

8.00 3RV10 21-1HA10 3RT10 24-1AP00 S0/S0 50 4 8.5 7.00 ... 10.0 3RV10 21-1JA10 3RT10 26-1AP00 S0/S0 50 5.5 11.5 9.00 ... 12.5 3RV10 21-1KA10 3RT10 26-1AP00 S0/S0 50 7.5 15.5 11.0 ... 16.0 3RV10 21-4AA10 3RT10 26-1AP00 S0/S0 50 7.5 15.5 14.0 ... 20.0 3RV10 21-4BA10 3RT10 26-1AP00 S0/S0 50 11 22 18.0 ... 25.0 3RV10 31-4DA10 3RT10 34-1AP00 S2/S2 50 15 29 22.0 ... 32.0 3RV10 31-4EA10 3RT10 34-1AP00 S2/S2 50 18.5 35 28.0 ... 40.0 3RV10 31-4FA10 3RT10 35-1AP00 S2/S2 50 22 41 36.0 ... 45.0 3RV10 31-4GA10 3RT10 36-1AP00 S2/S2 50 22 41 40.0 ... 50.0 3RV10 31-4HA10 3RT10 36-1AP00 S2/S2 50 30 55 45.0 ... 63.0 3RV10 41-4JA10 3RT10 44-1AP00 S3/S3 50 37 66 57.0 ...

75.0 3RV10 41-4KA10 3RT10 45-1AP00 S3/S3 50 45 80 70.0 ... 90.0 3RV10 41-4LA10 3RT10 46-1AP00 S3/S3 50 45 80 80.0 ... 100 3RV10 41-4MA10 3RT10 46-1AP00 S3/S3 50 55 97 40.0 ... 100 3VL27 10-2SP333) 3RT10 54-1AP36 –/S6 50 75 132 64.0 ... 160 3VL27 16-2SP33 3RT10 55-6AP36 –/S6 50 90 160 80.0 ... 200 3VL37 20-2SP363) 3RT10 56-6AP36 –/S6 50 110 195 80.0 ... 200 3VL37 20-2SP364) 3RT10 64-6AP36 –/S10 50 110 195 80.0 ... 200 3VL37 20-2SP364) 3RT12 64-6AP56 –/S10V 50 132 230 100 ... 250 3VL37 25-2SP365) 3RT10 65-6AP36 –/S10 50 132 230 100 ... 250 3VL37 25-2SP365) 3RT12 65-6AP36 –/S10V 50 160 280 125 ... 315 3VL47 31-2SP36 3RT10 66-6AP36 –/S10 50 160 280 125 ...

315 3VL47 31-2SP36 3RT12 66-6AP36 –/S10V 50 200 350 200 ... 500 3VL57 50-2SP36 3RT10 75-6AP36 –/S12 50 200 350 200 ... 500 3VL57 50-2SP36 3RT12 75-6AP36 –/S12V 50 250 430 200 ... 500 3VL57 50-2SP36 3RT10 76-6AP36 –/S12 50 250 430 200 ... 500 3VL57 50-2SP36 3RT12 76-6AP36 –/S12V 50