omron — Standard Connection Diagram

Standard Connection Diagram DC reactor (optional) Braking resistor (optional) R/L1 +1 P/+2 RB N/– S/L2 U/T1 V/T2 M T/L3 W/T3 3-phase 200 V AC 1/3-phase 200 V AC *1 3-phase 400 V AC Multi-function input 1 PSC Relay output *2 Multi-function input 2 S2 S1 MB NO contact Multi-function input 3 Multi-function input 4 S3 MA MC NC contact Multi-function input 5 S5 S4 Common Multi-function input 6 S6 P1 Multi-function output 1 Sequence input common SC P2 Multi-function output 2 Frequency reference power supply (20 mA at +12 V) Frequency reference (1 to 2 k Ω ) FS PC Multi-function output common Frequency reference input (voltage) FV Frequency reference input Frequency reference common FC AM Analog monitor output (4 to 20 mA) FI *1.

Connect a single-phase 200-V AC input to terminals R/L1 and S/L2. *2. By factory default, MA is set to NC contact, and MB to NO contact in the relay output (MA, MB) selection (C036). 34 Multi-functional Compact Inverters SYSDRIVE MX Series