*1. The reset command will not be accepted until approximately 10 seconds pass since the trip occurs (protection function works) *2. The reset command will not be accepted if the EEPROM error occurs. Turn off the power once. If you find E08 when turning on the power again, it is possible that the memory element has been broken or the parameters have not been memorized correctly. Perform the user initialization to set the parameters again. *3. The reset command through the RS terminal or STOP/RESET key will not be accepted. Turn off the power. *4. The reset operation via the Digital Operator will not be accepted. Be sure to reset via the RS terminal.
52 Advanced General-purpose Inverters SYSDRIVE RX Series Display on Digital Operator Name Description ek6k0. ek6k9. Option 1 error Detects an error on the board mounted on option slot 1. For details, refer to the operation manual for the mounted option board. ek7k0. ek7k9. Option 2 error Detects an error on the board mounted on option slot 2. For details, refer to the operation manual for the mounted option board. ek6k0. ek6k9. ek0k8.