omron — 2nd Control Function and Special 2nd Function

4-2 Function Mode 2nd Control Function and Special 2nd Function This function is used to operate by switching two different types of motors. 4 •By allocating 08 (SET) or 53 (SP-SET) to the desired multi-function input and then turning on/off the SET or SP-SET terminal, you can switch and control two different motors. •Switch to the 2nd control function at the SET terminal after turning off the RUN command and the Inverter output. •You can switch to the 2nd control function at the SP-SET terminal while in operation. •To display and set each parameter for the 2nd control (parameter No.200s), allocate the SET terminal.

Functions •To display and set each parameter for the 2nd control (parameter No.200s), allocate SET and SP- SET. •Parameters changeable while in operation are as follows: 4-51 Data Symbol Function name Status Description 08 SET 2nd control ON Enables the parameter for the 2nd motor. OFF Disables the parameter for the 2nd motor. 53 SP-SET Special 2nd function ON Enables the parameter for the special 2nd motor. OFF Disables the parameter for the special 2nd motor. Related functions C001 to C005 U/T1 V/T2 W/T3 Inverter SET /SP-SET SC Motor 1 Motor 2 Parameter No.

Function name Selection SET SP-SET F002/F202 Acceleration time 1 Yes Yes F003/F203 Deceleration time 1 Yes Yes A001/A201 Frequency reference selection No Yes A002/A202 RUN command selection No Yes A003/A203 Base frequency No Yes A004/A204 Maximum frequency No Yes A020/A220 Multi-step speed reference 0 Yes Yes A041/A241 Torque boost selection No Yes