4-2 Function Mode 4 Functions Multi-function Output Terminal Contact Selection This function allows you to set either contact for the two multi-function output terminals respectively. „ Specifications of the Multi-function Output Terminal P1 •Below are the specifications of the multi-function output terminal P1. Electrical specifications Between each terminal and PC Voltage drop 4 V max. at power-on Max. allowable voltage: 27 V DC Max. allowable current: 50 mA •The PC terminal acts as a common terminal at sink/source logics. 4-71 ON delay Original signal waveform (without delay) ON delay only OFF delay only ON and OFF delays ON delay OFF delay ON delay OFF delay Parameter No.
Function name Data Default setting Unit C031 Multi-function output terminal P1 contact selection 00: NO contact 01: NC contact 00 ⎯ C036 Relay output (MA, MB) contact selection 00: NO contact between MA and MC 01: NC contact between MA and MC 01 ⎯ Inside the Inverter PC P1 PC P1 C031 set value Power supply Output status 00 (NO contact) ON ON OFF OFF - 01 (NC contact) ON ON OFF OFF -