4-2 Function Mode 4 Functions *1. When either the control circuit terminal block or the coil is turned ON, these settings are ON. The control circuit terminal block has the priority for the multi-function input. If the master cannot reset the coil ON status due to communication disconnection, turn the control circuit terminal block from ON to OFF in order to turn OFF the coil. *2. The content of a communications error is retained until a fault reset is input. (Available to reset during operation) Holding Register Number List 4-92 Coil No. Item R/W Description 0015h Excessive PID deviation signal R 1: ON 0:
OFF 0016h Overload warning signal R 0017h Frequency arrival signal (Over set frequency) R 0018h Frequency arrival signal (At a constant speed) R 0019h Signal during RUN R 001Ah Data writing R 1: Writing 0: Normal 001Bh CRC error R 1: Error 0: No error *2 001Ch Overrun error R 001Dh Framing error R 001Eh Parity error R 001Fh Check sum error R Register No. Function name Parameter No. R/W Function Monitor or data range Resolution 0002h Frequency reference (Enable when A001 = 03) ⎯ R/W 0 to 4000 0.1 [Hz] 0003h Inverter status ⎯ R 00: Default 01: (Reserved) 02: Stop 03: Run 04: Free-run stop (FRS) 05: Jogging 06: DC injection braking 07: Retry 08: Trip 09:
Undervoltage ⎯ 0005h PID feedback (Enable when A076 = 02) ⎯ R/W 0 to 1000 0.1 [%] 1002h Output frequency monitor d001 R 0 to 4000 0.1 [Hz] 1003h Output current monitor d002 R 0 to 2000 0.1 [%] 1004h Rotation direction monitor d003 R 00: Stop 01: Forward 02: Reverse 1005h PID feedback value monitor (A075 PID scale) d004 (MSB) R 0 to 999900 0.01 [%] 1006h d004 (LSB)