4-2 Function Mode 4 Functions 4-101 Register No. Function name Parameter No. R/W Function Monitor or data range Resolution 10D6h STOP key selection b087 R/W 00: Enabled 01: Disabled ⎯ 10D7h Free-run stop selection b088 R/W 00: 0 Hz start 01: Frequency pull-in restart ⎯ 10D8h Monitor display selection b089 R/W 01: Output frequency monitor 02: Output current monitor 03: Rotation direction monitor 04: PID feedback value monitor 05: Multi-function input monitor 06: Multi-function output monitor 07: Frequency conversion monitor ⎯ 10DAh Stop selection b091 R/W 00: Deceleration→Stop 01: Free-run stop ⎯ 10DBh Cooling fan control b092 R/W 00: Always ON 01: ON during RUN 02:
Depends on the fin temperature ⎯ 10F5h Overvoltage LAD stop function b130 R/W 00: Disabled 01: Enabled ⎯ 10F6h Overvoltage LAD stop function level setting b131 R/W 200-V class: 330 to 395, 400-V class: 660 to 790 1. [V] 1176h Overvoltage protection function selection during deceleration b133 R/W 00: Disabled 01: Enabled ⎯ 1177h Overvoltage protection level setting during deceleration b134 R/W 200-V class: 330. to 395. 400-V class: 660. to 790. 1. [V] 10F7h Overcurrent suppression function b140 R/W 00: Disabled 01: Enabled ⎯ 10F8h Automatic carrier reduction b150 R/W 00: Disabled 01: Enabled ⎯ 10F9h Ready function selection b151 R/W 00: RDY disabled 01: RDY enabled ⎯