omron — Extended function mode

Appendix-1 Parameter List Appendix * 2nd control is displayed when SET (08) is allocated to one of from C001 to C005. App-8 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value External frequency adjustment A101 FI start frequency 0.0 to 400.0 0.0 No Hz A102 FI end frequency 0.0 to 400.0 0.0 No Hz A103 FI start ratio 0. to 100. 0. No % A104 FI end ratio 0. to 100. 100. No % A105 FI start selection 00: Use FI start frequency [A101] 01: 0 Hz start 01 No ⎯ Operation frequency A141 Operation frequency input A setting 00: Digital Operator (F001) 01: Digital Operator (FREQ adjuster) 02: Input FV 03: Input FI 04:

RS485 communication 01 No ⎯ A142 Operation frequency input B setting 02 No ⎯ A143 Operator selection 00: Addition (A + B) 01: Subtraction (A - B) 02: Multiplication (A × B) 00 No ⎯ Frequency addition A145 Frequency addition amount 0.0 to 400.0 0.0 Yes Hz A146 Frequency addition direction 00: Adds A145 value to output frequency 01: Subtract A145 value from output frequency 00 No ⎯ VR adjustment A151 VR start frequency 0.0 to 400.0 0.0 No Hz A152 VR end frequency 0.0 to 400.0 0.0 No Hz A153 VR start ratio 0. to 100. 0. No % A154 VR end ratio 0. to 100. 100. No % A155 VR start selection 00: Use VR start frequency [A151] 01: 0 Hz start 01 No ⎯