2-2 Wiring „ Specifications of the Control Circuit Terminals 2 Design 2-22 Terminal symbol Terminal name and function Default setting Specifications Input signal PSC External power supply terminal for input signal (input).......................At sink logic Internal power supply output terminal for input signal (output)......At source logic ⎯ 24 V DC ±10% 30 mA max. 24 V DC ±10% 100 mA max. S1 Multi-function input terminals S1 to S5 Select 5 functions among the 31 functions and allocate them to from terminals S1 to S5. The terminal allocation is changed automatically when the emergency shutoff function is used. Refer to "Emergency Shutoff Input Function" (page 4-45).

Forward/Stop Contact input Close: ON (Start) Open: OFF (Stop) Minimum ON time: 12 ms min. S2 Reverse/Stop S3 Fault reset S4 Emergency stop fault S5 Multi-step speed reference 1 SC Input signal common ⎯ Monitor signal AM Analog frequency monitor/ Analog output current monitor Analog frequency monitor Frequency reference input FS Frequency reference power supply ⎯ 10 V DC 10 mA max.

FV Voltage frequency reference signal ⎯ 0 to 10 V DC Input impedance 10 kΩ When installing variable resistors at FS, FV, and FC (1 to 2 kΩ) FI Current frequency reference signal ⎯ 4 to 20 mA DC Input impedance 250 Ω FC Frequency reference common ⎯ Output signal P1 Multi-function output terminal Select the status of the Inverter and allocate it to terminal P1. Frequency arrival signal at a constant speed 27 V DC 50 mA max. PC Output signal common ⎯ Relay output signal MA MB MA MC Contact ratings 250 V AC 2.0 A (resistance load) 100 V AC min. 0.2 A (inductive load) 10 mA Under normal operation :

MA-MC Closed 30 V DC 3.0 A (resistance load) 5 V DC Under abnormal operation or power 0.6 A (inductive load) 100 mA shutdown : MA-MC Open (Default) MB MC MB MA MC