3-2 Test Run Operation „ Setting the Motor Capacity Selection (H003) and Motor Pole Number Selection (H004) 3 Operation 3-6 Parameter No. Register No. Name Description Setting range Unit of setting Default setting Interrupt during RUN H003 1165h Motor capacity selection Sets the capacity of the motor connected to the Inverter. 200-V class 0.2/0.4/0.75/ 1.5/2.2/3.7/ 5.5/7.5 400-V class 0.4/0.75/1.5/ 2.2/3.7/5.5/7.5 kW Varies with the capacity. No H004 1166h Motor pole number selection Sets the pole number of the motor connected to the Inverter. 2/4/6/8 Pole 4 No Key sequence Display example Description bk-k-k- Press the Mode key twice to display the mode selection.
hk-k-k- Use the Increment or Decrement key to display "H---". hk0k0k3 Press the Mode key. "H003" is displayed. 0.2k0 Press the Mode key. The set value in "H003" is displayed. 0.4k0 Use the Increment or Decrement key to set the rated motor capacity. 0.4k0 Press the Enter key. The set value is entered. (In approx. 1 s) hk0k0k3 The parameter number is displayed again.