3-7 Parameter List 3 Operation * 2nd control is displayed when SET (08) is allocated to one of from C001 to C005. 3-31 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Page Others b086 Frequency conversion coefficient 0.1 to 99.9 1.0 Yes ⎯ 4-39 b087 STOP key selection 00: Enabled 01: Disabled 00 No ⎯ 4-39 b088 Free-run stop selection 00: 0 Hz start 01: Frequency pull-in restart 00 No ⎯ 4-39 4-53 b089 Monitor display selection 01: Output frequency monitor 02: Output current monitor 03: Rotation direction monitor 04: PID feedback value monitor 05: Multi-function input monitor 06: Multi-function output monitor 07:
Frequency conversion monitor 01 Yes ⎯ 4-40 b091 Stop selection 00: Deceleration → Stop 01: Free-run stop 00 No ⎯ 4-39 b092 Cooling fan control 00: Always ON 01: ON during RUN 02: Depends on the fin temperature 01 No ⎯ 4-40 b130 Overvoltage LAD stop function 00: Disabled 01: Enabled 00 No ⎯ 4-41 b131 Overvoltage LAD stop function level setting 200-V class: 330. to 395. 400-V class: 660. to 790. 380/ 760 Yes V 4-41 b133 Overvoltage protection function selection during deceleration 00: Disabled 01: Enabled 00 No ⎯ 4-35 b134 Overvoltage protection level setting during deceleration 200-V class: 330. to 395. 400-V class: 660. to 790. 380/ 760 No V 4-35 b140 Overcurrent suppression function 00:
Disabled 01: Enabled 01 No ⎯ 4-42 b150 Automatic carrier reduction 00: Disabled 01: Enabled 00 No ⎯ 4-42 b151 Ready function selection 00: Disabled 01: Enabled 00 No ⎯ 4-42