4-1 Monitor Mode Multi-function Input Monitor [d005] Displays the input status of the multi-function input terminals. C011 to C015 (contact selection) are excluded. (Example) Multi-function input terminals S4, S2 : ON Multi-function input terminals S5, S3, S1 : OFF Display : ON ON OFF : OFF S1 S2 S3 S4 S5 4 (OFF) (ON) (OFF) (ON)(OFF) Multi-function input monitor Multi-function Output Monitor [d006] Functions Displays the output status of the multi-function output terminals and relay output terminals. C031 and C036 (contact selection) are excluded. This monitor indicates the signal status of the functions (C021 and C026) allocated to each multi- function output terminal.
(Example) Multi-function output terminal P1 : ON Relay output terminal MA : OFF ON Display : ON OFF : OFF P1 MA (OFF) (ON) Multi-function output monitor Output Frequency Monitor (After Conversion) [d007] Displays a conversion value obtained by multiplying the Inverter output frequency by the coefficient set in [b086]. Displayed value = "Output frequency [d001]" Ч "Frequency conversion coefficient [b086]" (Display) [d007] 0.00 to 99.99 : Displays in increments of 0.01. 100.0 to 999.9 : Displays in increments of 0.1. 1000. to 9999. : Displays in increments of 1. 1000 to 3996 : Displays in increments of 10. (Setting range) [b086] 0.1 to 99.9: Can be set in increments of 0.1.
(Example) When the output frequency [d001] = 50.0 Hz, and the frequency conversion coefficient [b086] = 1.1, the monitor [d007] displays "55.0" through 50.0 Ч 1.1 = 55.0. 4-2