4-2 Function Mode Frequency Reference Selection Select the method of the frequency reference. 4 * To switch to the 2nd frequency reference, allocate 08 (SET) to the multi-function input terminal and then turn it on. Functions RUN Command Selection Select the method of the RUN/STOP command. * To switch to the 2nd RUN command, allocate 08 (SET) to the multi-function input terminal and then turn it on. 4-7 Parameter No. Function name Data Default setting Unit A001 Frequency reference selection 00: Digital Operator (FREQ adjuster) 01: Terminal 02: Digital Operator (F001) 03: ModBus communication 10:
Frequency operation result 00 ⎯ * A201 2nd frequency reference selection Related functions A005, A141 to A143, A145, A146 Data Frequency reference source 00 FREQ adjuster 01 Voltage or current directive from the terminal. 02 F001 value set via the Digital Operator. 03 ModBus communication 10 Result of the frequency operation function Parameter No. Function name Data Default setting Unit A002 RUN command selection 01: Terminal 02: Digital Operator 03: ModBus communication 02 ⎯ * A202 2nd RUN command selection Related functions F004, A005, C001 to C005 Data RUN command source 01 Turn ON/OFF the FW and RV allocated to the terminal.
The STOP command is activated if both Forward/Reverse commands are input simultaneously. 02 Use the STOP/RESET key on the Digital Operator. 03 Use the ModBus communication.