HANDLING 12. Handling and installation instructions for the KUAX 671 12.1. Handling instructions = Storage temperature: - 25 °C to + 85 °C - The usual precautions are to be observed to protect against the effects of static electricity. 12.2. Installation instructions - The KUAX 671 cam controller is to be installed in such a way that heat will not accumulate. = The maximum permissible ambient temperature of 55 °C may not be exceeded. ‘The shielding must always be connected (pin 23 at the 25pole D-sub plug) when lengthening the transducer cable. - Only a single conductor may be connected at each terminal.
- Operating voltage and the control line (24 V DC) are to be routed separately within the switching cabinet. Use separate cables outside the switching cabinet. = The outputs are equipped with diodes to suppress inductive voltage peaks. If, however, there is a switch between the outputs and the using unit the latter must also be fitted with a diode. - No outside voltages may be applied to the outputs. ‘The user must always observe the VDE-recommendations and other applicable regulations when working with or on the system. 57