7 Troubleshooting ‹ Operator Programing Errors An Operator Programming Error (OPE) occurs when an inapplicable parameter is set or an individual parameter setting is inappropriate. This monitor will display the parameter that is causing the OPE error. 26 I80E-EN J1000 Quick Start Guide LED Operator Display Cause Corrective Action oPE01 Drive capacity and value set to o2-04 do not match. Correct the value set to o2-04. oPE02 Parameters were set outside the allowable setting range. Set parameters to the proper values. oPE03 A contradictory setting is assigned to multi-func- tion contact inputs H1-01 through to H1-05.
• The same function is assigned to two inputs (this excludes “External fault” and “Not used”) • Input functions which require the setting of other input functions were set alone. • Input functions that are not allowed to be used simultaneously have been set. • Fix any incorrect settings. • Refer to the instruction manual for more details. oPE05 No option unit is installed and one of the follow- ing is true: • b1-01=2 or 3 • b1-02=2 • Install the required option unit. • Correct the values set to b1-01 and b1-02. oPE10 The V/f pattern setting is incorrect. • Check the V/f pattern settings. • Refer to the instruction manual for more details.