omron — Precautions for UL/cUL Standards Compliance

1 Safety Instructions and General Warnings ‹ Precautions for CE Low Voltage Directive Compliance This drive has been tested according to European standard EN61800-5-1: 2007, and it fully complies with the Low Voltage Directive. The following conditions must be met to maintain compliance when combining this drive with other devices: Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3 in accordance with IEC664. Ground the neutral point of the main power supply for 400 V Class drives. ‹ Precautions for UL/cUL Standards Compliance This drive is tested in accordance with UL standard UL508C and complies with UL require- ments.

The following conditions must be met to maintain compliance when using this drive in combination with other equipment: Do not install the drive to an area greater than pollution severity 2 (UL standard). Use UL-listed copper wires (rated at 75 ° C) and closed-loop connectors or CSA-certified ring connectors. For details refer to the instruction manual. Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. Use a class 2 (UL regulations) power supply for the control circuit termi- nal. For details refer to the instruction manual.

This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current flow will not rise above 30,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives. The drive internal motor overload protection is UL listed and in accordance with the NEC and CEC. The setup can be done using the parameters L1-01/02. For details refer to the tech- nical manual. 8 I80E-EN J1000 Quick Start Guide