Delta Electronics — 2.2.4.2 Electrical Specifications for Temperature / Current / Analog Input Terminals

TP70P-211LC1T/TP04P-20EXL1T Operation Manual 2.2.4 Analog Input/Output Specifications 2.2.4.1 Electrical Specifications for Analog Output Terminals _ 2 2.2.4.2 Electrical Specifications for Temperature / Current / Analog Input Terminals 2-14 Model TP70P-211LC1T / TP04P-20EXL1T Item Number of channels for 4 (IO1~IO4) analog output Analog output range 4 ~ 20 mA, 0 ~ 20 mA Digital conversion range 0 ~ 32000 Resolution 15 bits Output impedance 100 Ω When reached full scale at 25℃ (77℉), the range of error is ±0.2%. When reached full scale between 0~55℃ (32~131℉), the range of error is ±0.5%.

Overall accuracy Response time 2 ms Isolation No isolation Maximum output current (Allowable load) Protection Short circuit protection Model TP70P-211LC1T / TP04P-20EXL1T Item Number of channels 2 (L1, L2) for analog input Input form Thermal resistance Voltage / current input mode (divider type) 2-wired / 3-wired Pt100, JPt100, Pt1000, Cu50, Cu100, Ni100, Ni1000, LG-Ni1000 - Applicable sensor - Voltage: 0 ~ 5V, 0 ~ 10V, 0 ~ 50mV Current: 0 ~ 20mA, 4 ~ 20mA Analog input range When reached full scale at 25℃ (77℉), the range of error is ±0.4%. When reached full scale between 0~55℃ (32~131℉), the range of error is ±0.8%. When reached full scale at 25℃ (77℉), the range of error is ±0.5%.

When reached full scale between 0~55℃ (32~131℉), the range of error is ±1%. Overall accuracy Response time 260 ms 130 ms Digital conversion 0 ~ 32000 0 ~ 32000 range Analog input 16 bits resolution Thermal conductivity 100 m - Self-diagnosis Disconnection detection - 2 MΩ Voltage: 650 KΩ, divider type Current: 249 Ω Input impedance