User Manual of EM730 Series Inverter 126 frequency arrival (FAR) F15.21 Output frequency detection FDT1 0.00 to maximum frequency F00.16 Hz 30.00 〇 0x0F15 F15.22 FDT1 hysteresis -(Fmax-F15.21)~F15.21 Hz 2.00 〇 0x0F16 F15.23 Output frequency detection FDT2 0.00 to maximum frequency F00.16 Hz 20.00 〇 0x0F17 F15.24 FDT2 hysteresis -(Fmax-F15.23)~F15.23 Hz 2.00 〇 0x0F18 F15.25 Options of analog level detection ADT 0:AI1 1:AI2 0 ○ 0x0F19 F15.26 Analog level detection ADT1 0.00 ~ 100.00 % 20.00 ● 0x0F1A F15.27 ADT1 hysteresis 0.00 to F15.26 (valid down in one direction) % 5.00 ● 0x0F1B F15.28 Analog level detection ADT2 0.00 ~ 100.00 % 50.00 ● 0x0F1C F15.29 ADT2 hysteresis 0.00 to F15.28 (valid down in one direction) % 5.00 ● 0x0F1D F15.30 Options of energy consumption braking function 0:
invalid 1: valid 0 〇 0x0F1E F15.31 Energy consumption braking voltage 110.0 ~ 140.0 (380V, 100.0 = 537V) % 125.0 〇 0x0F1F F15.32 Braking rate 20 ~ 100 (100 means that duty ratio is 1) % 100 ● 0x0F20 F15.33 Operating mode with set frequency less 0: running at the lower frequency limit 1: shutdown 2: zero-speed running 0 〇 0x0F21