User Manual of EM730 Series Inverter status of the F/R terminal and the set value of F00.20. If the set forward running direction of the inverter is inconsistent with the desired rotation direction of the motor, exchange any two of the output terminal wires (U, V, W) of the inverter, or set F00.20 to the opposite value. Increasing the carrier frequency can reduce the motor noise, but will lead to the heat increase of the inverter. When the carrier frequency is higher than the default value and increased by 1kHz, the load needs to be derated to some extent. Please set F00.24=1. The actual carrier frequency of the inverter will be adjusted automatically according to the actual situation.
The recommended relationship between the rated power and carrier frequency of the inverter is shown in Table 7-4. Table 7- 4 Relationship between Rated Power and Carrier Frequency Setting of Inverter 164 Function code Function code name Parameter description Unit Default setting Attribute mailing address F00.23 Carrier frequency 1.0~16.0 (rated power of the inverter: less than 4.00kW) 1.0~10.0 (rated power of the inverter: 5.50~7.50kW) 1.0~8.0 (rated power of inverter 11.00 - 45.00kW) 1.0~4.0 (rated power of inverter 55.00 - 90.00kW) 1.0~3.0 (rated power of inverter:
110.00kW and above) kHz 4.0 (7.5 and below) /2.0 ● 0x0017 Inverter power Pe Pe≤4kW 5.5kW~7.5kW 11kW~ 45kW 55kW~ 90kW 110kW~ 560kW Rated carrier frequency 4.0kHz 2.0kHz Maximum allowable carrier frequency 16.0 kHz 10.0kHz 8.0kHz 4.0kHz 3.0kHz Function code Function code name Parameter description Unit Default setting Attribute mailing address F00.24 Automatic adjustment of carrier 0: invalid 1: valid 1 2: valid 2 1 〇 0x0018