User Manual of EM730 Series Inverter needed when the terminal status is read, in order to avoid interference. ★ The parameters of this code do not need to be adjusted under normal circumstances. Where adjustment is required, pay attention to the relationship between the filtering time and terminal action duration, to avoid the susceptibility to interference due to insufficient filtering times or slow responses and command losses arising from excessive filtering times. In the event of changes in the status of the function terminal, a response will be made with Fig. 7- 14 Schematic Diagram of Terminal Delay Sampling delay according to the function code settings.

Currently only the terminals X1 to X4 support this function. Specifically, it is embodied in: This function will take effect when the function terminal changes from the invalid to valid status and is maintained with the valid delay, and not take effect when the function terminal changes from the valid to invalid status and is maintained with the invalid delay. ★ If the function code is set to 0.000s, the corresponding delay will be invalid.

181 Function code Function code name Parameter description Unit Default setting Attribute mailing address F02.18 X1 valid delay time 0.000~30.000 s 0.000 ● 0x0212 F02.19 X1 invalid delay time 0.000~30.000 s 0.000 ● 0x0213 F02.20 X2 valid delay time 0.000~30.000 s 0.000 ● 0x0214 F02.21 X2 invalid delay time 0.000~30.000 s 0.000 ● 0x0215 F02.22 X3 valid delay time 0.000~30.000 s 0.000 ● 0x0216 F02.23 X3 invalid delay time 0.000~30.000 s 0.000 ● 0x0217 F02.24 X4 valid delay time 0.000~30.000 s 0.000 ● 0x0218 F02.25 X4 invalid delay time 0.000~30.000 s 0.000 ● 0x0219