sinee — 7.9Multi-segment Speed and Simple PLC Parameter Group

User Manual of EM730 Series Inverter Fig. 7-26 Schematic Diagram of Simple PLC Operation Since the running time of the 3 rd segment is set to 0 (F08.24=0.0), the 3 rd segment will not be put Fig. 7- 26 shows the operation diagram in the running mode “0: stop after a single run”. into actual operation. The running time of the 14 th and 15 th segments is set to 0 (F08.46=0.0, F08.48=0.0), so the last segment is the 13 th segment, and the inverter will be stopped after running in the 13 th segment. The PLC stop memory is to record the current simple PLC running times (F18.10), running stage (F18.11), and running time at the current stage (F18.12).

The inverter will continue to run from the memory stage during next operation. If you choose no memory, the PLC process will be performed every time the inverter is started. 230 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F08.17 Simple PLC memory options Ones place: stop memory options 0: no memory (from the first segment) 1: memory (from the moment of stop) Tens place: power-down memory options 0: no memory (from the first segment) 1: memory (from the power-down moment) 00 ● 0x0811