sinee — 7.13Keyboard and Display Function Parameter Group of F

User Manual of EM730 Series Inverter display are dependent on the settings of the function codes F12.04 to F12.08. For the selected F12.32=0 : monitoring mode 0. The LED switching display and LCD small-line (7-line) function codes, please refer to their parameter description. F12.32=1 : monitoring mode 1. The LED switching display and LCD small-line (7-line) display are dependent on the settings of the function codes F12.33 to F12.37. You can select any function code. F12.33=18.00 means that the function code F18.00 is displayed. The UP/DOWN function is valid. When F12.41=0, the UP/DOWN function can reduce the output frequency of the inverter to 0 without reversing.

When F12.41=1, the UP/DOWN function can reduce the output frequency of the inverter to 0, followed by reverse running of the motor. For the digital potentiometer setting, see the setting of the main frequency source A.

264 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F12.33 Running status display parameter 1 of Mode 1 (LED stop status display parameter 5) 0.00 ~ 99.99 18.00 ● 0x0C21 F12.34 Running status display parameter 2 of Mode 1 (LED stop status display parameter 1) 0.00 ~ 99.99 18.01 ● 0x0C22 F12.35 Running status display parameter 3 of Mode 1 (LED stop status display parameter 2) 0.00 ~ 99.99 18.06 ● 0x0C23 F12.36 Running status display parameter 4 of Mode 1 (LED stop status display parameter 3) 0.00 ~ 99.99 18.08 ● 0x0C24 F12.37 Running status display parameter 5 of Mode 1 (LED stop status display parameter 4) 0.00 ~ 99.99 18.09 ● 0x0C25 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F12.41 Options of UP/DOWN zero crossing 0:

prohibit zero crossing 1: allow zero crossing 0 〇 0x0C29