User Manual of EM730 Series Inverter F14.77=0 : the acceleration/deceleration time of the motor 2 is the same as that of the motor 1. For details, see the description of the function codes F15.03 to F15.09; F14.77=1/2/3/4 : the acceleration/deceleration time of the motor 2 is fixed as the acceleration/deceleration time 1/2/3/4, corresponding to the function codes F00.14, F00.15/F15.03, F15.04/F15.05, F15.06/F15.07 and F15.08, respectively.
See F00.16 and F00.18 272 Function code Function code name Parameter description Unit Default setting Attribute Mailing address F14.78 Maximum frequency of motor 2 20.00~600.00 Hz 50 〇 0x0E4E F14.79 Upper frequency limit of motor 2 Lower limit frequency F00.19 to maximum frequency F14.78 Hz 50 ● 0x0E4F Function code Function code name Parameter description Unit Default setting Attribute Mailing address F14.80 V/F curve setting of motor 2 0: straight line V/F 1: multi-point broken line V/F 2: 1.3-power V/F 3: 1.7-power V/F 4: square V/F 5: VF complete separation mode (Ud = 0, Uq = K * t = voltage of separation voltage source) 6:
VF semi-separation mode (Ud = 0, Uq = K * t = F/Fe * 2 * voltage of separation voltage source) 0 〇 0x0E50 F14.81 Multi-point VF frequency F1 of motor 2 0.00 ~ F14.83 Hz 0.50 ● 0x0E51 F14.82 Multi-point VF voltage V1 of motor 2 0.0~100.0 (100.0 = Rated voltage) % 1.0 ● 0x0E52 F14.83 Multi-point VF frequency F2 of motor 2 F14.81 ~ F14.85 Hz 2.00 ● 0x0E53 F14.84 Multi-point VF voltage V2 of motor 2 0.0~100.0 % 4.0 ● 0x0E54