User Manual of EM730 Series Inverter After the corresponding application macro is selected by changing the function code, F12.14 will be executed automatically to restore the default settings, and the parameters will be restored the macro-specific parameters. The length counting function is performed by entering the length information from the digital EM730 series inverters have a fixed-length counting function, as shown in Figure 7-40. input terminal in the pulse form and then setting the related function code. The final length count information can be outputted by the digital output terminal for other purposes (e.g. DI/VX input as the stop command).
Users can also view the real-time length count via F18.34. The length resolution can be set by F16.13. In case of any change in the length resolution, F16.01 will change accordingly. For example, if F16.13 is set to 0:1m, the setting range of F16.01 is 1-65535m. Fig. 7-40 Block Diagram of Fixed-length Counting 304 Function code Function code name Parameter description Uni t Defaul t setting Attribut e Mailing address F16.01 Set length 1 ~ 65535 (F16.13=0) 0.1 ~ 6553.5 (F16.13=1) 0.01 ~ 655.35 (F16.13=2) 0.001 ~ 65.535 (F16.13=3) m 1,000 ● 0x1001 F16.02 Pulses per meter 0.1 ~ 6553.5 100.0 ● 0x1002 F16.13 Set length resolution 0:1m 1:0.1m 2:0.01 m 3:0.001m 0 〇 0x1003