User Manual of EM730 Series Inverter 347 selection Can be connected to the relay that controls the sleep pump F03.02 R1 output function selection 7: Fault output 7 F05.00 V/F curve setting 4: Square V/F curve 4 F07.06 Bus voltage control selection Units: Instantaneous stop without stopping function selection 0: Invalid 1: Deceleration Tens: Overvoltage stall function selection 1: Valid 11 F07.14 Failure retry times 0 to 20 times, 0: Retry is prohibited 5 retries are allowed for normal faults 5 F07.16 Failure retry interval 30s 30.00 F09.00 PID given source 0:
Digital PID given F09.01 F09.01 Target pressure setting 0.00~Pressure sensor range F09.03 bar 3.00 F09.02 PID feedback source 1:AI1 2:AI2 2 F09.03 Pressure sensor range 0.01~600.00 bar 10.00 F09.05 Proportional gain 1 0.00~100.00 3.00 F09.06 Integration time 1 0.000~30.000, 0.000:no integration s 1.00 F09.07 Derivative time 1 0.000~30.000 ms 0.000 F09.27 Sleep control selection 0: No sleep 3: Sealed tube sleep 0 F09.29 Sleep delay time 0.0~6500.0 s 60.0 F09.30 Wake-up stress 0.00~Pressure sensor range F09.03 bar 2.00 F09.31 Wake-up delay time 0.0~6500.0 (0.0 turns off wake-up) s 0.5 F09.39 Wake-up method selection 0: Target pressure F09.01*wake-up pressure Coefficient 1:
Wake-up pressure (F09.30) 1