sinee — 5.7.1 Parameter identification steps

User Manual of EM730 Series Inverter  Set F01.34=1 for confirmation and press the RUN key. The inverter will start the static self-identification of the motor.  Or, set F01.34=2 and press the RUN key. The inverter will start the rotary self-identification of the motor.  For the synchronous motor:  Set F01.34=11 and press the RUN key. The inverter will start the static self-identification of the motor.  Or, set F01.34=12 and press the RUN key. The inverter will start the rotary self-identification of the motor.  It takes about two minutes to complete the self-identification of the motor. Then the system will return to the initial power-on status from the “tune” interface.

 If multiple motors are used in parallel, the rated power and rated current input of the motors should be the sum of power and current of these motors.  If two motors are used alternately, the parameters of the motor 2 in the F14 group need to be set separately, and identified based on F14.34. 68