User Manual of EM760 High-Performance Inverter F08.44=5.0 : the operating time in the 13 th segment is 5.0s (F08.18=0 by default). 6.2.4 Main and auxiliary operation frequency As shown below, there are 6 types ofmain and auxiliary operations, in which both the main and the auxiliary settings are valid. Fig. 6-11 Setting diagram of main and auxiliary operation frequency Select the main and auxiliary operation mode. The final results are limited by the lower frequency limit (F00.19) and upper frequency limit (F00.18). F00.08=0: main frequency source A + auxiliary frequency source B The main and auxiliary operation result is the sum of the two items, and may be positive or negative.
That is, the result of the forward 20.00Hz and reverse 40.00Hz is reverse 20.00Hz. F00.08=1: main frequency source A - auxiliary frequency source B The main and auxiliary operation result is the difference between the two items, and may be positive or negative. That is, the result of the forward 20.00Hz and reverse 40.00Hz is forward 50.00Hz (upper frequency limit F00.18=50.00). 104 Function code Function codename Parameter description Unit Default setting Attribute F00.08 Options of main and auxiliary operation 0: main frequency source A + auxiliary frequency source B 1: main frequency source A - auxiliary frequency source B 2: larger value of main and auxiliary frequency sources 3:
smaller value of main and auxiliary frequency sources 4: main frequency source A - auxiliary frequency source B, and the result is greater than or equal to zero 5: main frequency source A + auxiliary frequency source B, and the result is greater than or equal to zero 0 〇