sinee — 6.5.1 Digital input terminal (DI)

User Manual of EM760 High-Performance Inverter The terminals X1 to X10, AI1 to AI4 are fourteen multi-function input terminals. The functions of the input terminals can be defined by setting the values ofthe function codes F02.00 to F02.13. For example, ifyou define F02.00=1, the function ofthe X1 terminal is “RUN”. Ifthe command source is set to terminal control (F00.02=1) and the X1 terminal input is valid, the “RUN” function of the inverter will be enabled. Specific options are described in the table below. Ifmultiple terminals are set to the same function (except for #34 function terminal),the function status is dependent on the “OR logic” of the two terminals.

In the case ofF02.00=1 and F02.04=1, once one of the terminals X1 or X5 is valid, the “RUN” function of the inverter will be enabled.

Table 6-12 Function List of Multi-function Digital Input Terminals 120 F02.03 Options ofX4 digital input function 12 〇 F02.04 Options ofX5 digital input function 13 〇 F02.05 Options ofX6 digital input function 14 〇 F02.06 Options ofX7 digital input function 10 〇 F02.07 Options ofAI1 digital input function 0 〇 F02.08 Options ofAI2 digital input function 0 〇 F02.09 Options ofAI3 digital input function 0 〇 F02.10 Options ofAI4 digital input function 0 〇 F02.11 Options ofX8 digital input function F02.12 Options ofX9 digital input function F02.13 Options ofX10 digital input function Settings Function Description 0 No function Disable the protection terminal or set it to “0:

Unavailable” to prevent malfunction. 1 Running terminal (RUN) When the command source is set to terminal control (F00.02=1), and the function terminal is valid, the inverter will execute the corresponding RUN function according to the set value ofthe terminal control mode option (F00.03). (See 6.1.2 for details) 2 Running direction F/R When the command source is set to terminal control (F00.02=1), and the function terminal is valid, the inverter will execute the corresponding F/R function according to the set value of the terminal control mode option (F00.03).

(See 6.1.2 for details) 3 Stop control of three-line operation When the command source is set to terminal control (F00.02=1), the terminal control mode is set to three-line control (F00.03=2/3) and the function terminal is valid, the inverter will execute the stop command. (See 6.1.2 for details)