User Manual of EM760 High-Performance Inverter 124 32 simple PLC time pause (keep running at current segment) When this terminal is valid, the simple PLC module will keep running at the current segment. When this terminal is invalid, the simple PLC module will continue to run after running at the current segment. 33 Reserved 34 counter input (≤250Hz) It is a pulse input terminal that has the counting function. The input pulse frequency is limited to 250Hz or below, and only one terminal can be set with this function. See 6.6.12 for details. 35 High speed counter input (≤ 100 kHz, only valid for X7) It is a pulse input terminal that has the counting function.
The input pulse frequency is limited to 100kHz or below. This is valid only for the terminal X7 (that is, only F02.06=35 can be set). See 6.6.12 for details. 36 Count clearing This terminal is used to clear the counter that has a counting function. 37 Length counter input (≤ 250Hz) It is a pulse input terminal that has the length counting function. The input pulse frequency is limited to 250Hz or below, and only one terminal can be set with this function. See 6.6.13 for details. 38 High-speed length counting input (≤ 100kHz, only valid for X7) It is a pulse input terminal that has the length counting function. The input pulse frequency is limited to 100kHz or below.
This is valid only for the terminal X7 (that is, only F02.06=38 can be set). See 6.6.13 for details. 39 Length clearing This length clearing terminal has a length counting function. 40 Pulse input (≤ 100 kHz, only valid for X7) This is a pulse signal input terminal, and the input pulse frequency is limited to 100kHz or below. It is valid only for the terminal X7. *: This is used only to set the equivalent AI percentage instead ofother special functions (e.g. counting). When F00.04=5, you need to set F02.06=40 and the set frequency pulse needs to be inputted from the terminal X7.
41 Process PID pause When this terminal is valid, PID adjustment will be stopped, and the output of the process PID module will remain unchanged. For more information, refer to 6.2.3.1 function code F09.18. 42 Process PID integral pause When this terminal is valid, the PID integral adjustment will be suspended, but the proportional and differential adjustment of the PID will be still valid. This function is known as integral separation. See the F09.20 description of 6.2.3.1. 43 PID parameter switching If the digital input terminal (F09.11=1) for PID parameter switching is valid, PID parameters will be switched. See the description of the function codes F09.05 to F09.13 under 6.2.3.1.