sinee — 6.5.2 Digital output terminal (DO)

User Manual of EM760 High-Performance Inverter Fig. 6-24 Schematic Diagram of Level and Single Pulse Output of Digital Output Terminal When the status of the selected function changes, the corresponding output terminal will make a response with delay based on the function code settings. At present, the terminals Y1 andR1 support this function. Details under default conditions: When the function changes from the invalid to valid status and is maintained with the valid delay, the corresponding output terminal will output the active level.

When the function changes from the valid to invalid status and is maintained with the invalid delay, the corresponding output terminal will output the inactive level. * If the function code is set to 0.000s, the delay will be invalid. When one function output terminal is in the single pulse output mode (see F03.05 for details), the pulse width of the active level can be controlled by setting the single pulse output time, in order to meet different process or control requirements.

135 Function code Function codename Parameter description Unit Default setting Attribute F03.09 Y1 valid delay time 0.000~30.000 s 0.000 ● F03.10 Y1 invalid delay time 0.000~30.000 s 0.000 ● F03.13 R1 valid delay time 0.000~30.000 s 0.000 ● F03.14 R1 invalid delay time 0.000~30.000 s 0.000 ● Function code Function codename Parameter description Unit Default setting Attribute F03.17 Single pulse time of Y1 output 0.001~30.000 s 0.250 ● F03.18 Single pulse time of Y2 output 0.001~30.000 s 0.250 ● F03.19 Single pulse time ofR1 output 0.001~30.000 s 0.250 ● F03.20 Single pulse time ofR2 output 0.001~30.000 s 0.250 ● Function code Function codename Parameter description Unit Default setting Attribute F03.31 Control logic options of PLC output terminal D7 D6 D5 D4 D3 D2 D1 D0 00*0000 ● * R4 R3 * R2 R1 Y2 Y1 0:

no output 1: Output