sinee — 6.5.8 Analog output terminal (AO)

User Manual of EM760 High-Performance Inverter * Fmax, maximum frequency (F00.16, and F14.78 when using motor 2) Ie, rated current of the inverter (F12.21) Ue, rated voltage of the inverter (F12.20) Pe, rated power of the inverter (F12.19) The above function codes are usually used to correct the zero drift of analog output and the deviation of output amplitude. They can also be used to customize the required AO output curve to meet the requirements of different instruments or others. If the offset is represented by “b”, the gain by “k”, actual output by “Y” and standard output by “X”, the actual output is: Y=kX + b. The M1 output type is controlled by F03.34: F03.34=0:

output voltage 0-10V 146 10 AI3 11 AI4 (expansion card) 12 High-frequency pulse input (with 100% corresponding to 100.00kHz) The function codes F02.26-F02.28 correspond to the output 0.0%- 100.0%.

13 Communication setting 1 Communication setting by M1 terminal, communication address option 701AH 14 Count value 0 to F16.03, corresponding to the output F16.10 to F16.11 15 Length value 0 to F16.01, corresponding to the output F16.10 to F16.11 16 PID output percentage -100.0% to 100.0%, corresponding to the output 0.0% to 100.0% 18 PID feedback -100.0% to 100.0%, corresponding to the output 0.0% to 100.0% 19 PID setting -100.0% to 100.0%, corresponding to the output 0.0% to 100.0% Function code Function codename Parameter description Unit Default setting Attribute F03.27 M1 output bias -100.0~100.0 % 0.0 ● F03.28 M1 output gain -9.999~9.999 1.000 ● F03.29 M2 output bias -100.0~100.0 % 0.0 ● F03.30 M2 output gain -9.999~9.999 1.000 ● Function code Function codename Parameter description Unit Default setting Attribute F03.34 Output type options of analog output M1 0:

0~10V 1: 4~20mA 2: 0~20mA 0 O F03.35 Output type options of analog output M2 0: 0~10V 1: 4~20mA 2: 0~20mA 1 O