User Manual of EM760 High-Performance Inverter 291 F03.03 Options of R2 output function (RA-RB-RC) 6: jog 7: inverter fault 8 O 0x0303 F03.04 Reserved 0 O 0x0304 8: inverter ready to run 9: reach the upper frequency limit 10: reach the lower frequency limit 11: valid current limit 12: valid overvoltage stall 13: complete simple PLC cycle 14: reach the set count value 15: reach the specified count value 16: reach the length 17: motor overload pre-alarm 18: inverter overheat pre-alarm 19: reach the upper limit of PID feedback 20: reach the lower limit of PID feedback 21: analog level detection ADT1 22: analog level detection ADT2 24: undervoltage state 25: motor overheat pre-alarm 26:
up to the set time 27: zero-speed running 38: off-load 39: Zero-speed running 2 40: Current reached 41: Torque reached 42: up to the speed 47: PLC output 59: Sleep indicator 67: Brake control 68: Material cutoff detection output 69: FDT1 lower limit (pulse) 70: FDT2 lower limit (pulse) 71: FDT1 lower limit (pulse, invalid in JOG) 72: FDT2 lower limit (pulse, invalid in JOG) 73: Overcurrent status 86: STO failure indication F03.05 Options of output signal type D7 D 6 D5 D4 D3 D2 D1 D0 0000 O 0x0305 * * * * R2 R1 Y2 Y1 0: level 1: single pulse F03.06 Positive/negative logic of digital output D7 D 6 D5 D4 D3 D2 D1 D0 000000 O 0x0306 * R 4 R3 * R2 R1 Y2 Y1 0:
positive logic is valid in the closed state/invalid in the open state 1: negative logic is valid in the closed state/invalid in the open state F03.07 Options of Y2 output type 0: ordinary digital 1: high frequency pulse output output 0 O 0x0307 F03.08 Output status control in jog D7 D 6 D5 D4 D3 D2 D1 D0 00000 O 0x0308 * * * RE V FD T 2 FD T 1 FAR RUN 0: valid in jogging 1: invalid in jogging