sinee — Chapter 11 Function Code Table

User Manual of EM760 High-Performance Inverter 304 F07.06 Bus voltage control options Ones place: Instantaneous stop/no-stop function options 0: Invalid 1: deceleration 2: deceleration to stop Tens place: Overvoltage stall function options 0: invalid 1:

valid 10 O 0x0706 F07.07 Voltage of overvoltage stall control 110.0~150.0(380V,100.0=537V) % 134.1 O 0x0707 F07.08 Instantaneous stop/no-stop operating voltage 60.0 to instantaneous stop/no-stop recovery voltage (100.0 = standard bus voltage) % 76.0 O 0x0708 F07.09 Instantaneous stop/no-stop recovery voltage Instantaneous stop/no-stop recovery voltage~100.0 % 86.0 O 0x0709 F07.10 Check time for instantaneous stop/no-stop recovery voltage 0.00~100.0 s 0.50 O 0x070A F07.11 Current limit control 0: Invalid 1: limit mode 1 2: limit mode 2 2 O 0x070B F07.12 Current limit level 20.0-180.0(100.0 = the rated current of inverter) % 150.0 ● 0x070C F07.13 Quick current limit options 0: Invalid 1:

valid 0 O 0x070D F07.14 Number of retries after failure 0: disable retry after 0~20, failure 0 O 0x070E F07.15 Options of digital output action in retries after failure 0: no action 1: action 0 O 0x070F F07.16 Interval of retries after failure 0.01~30.00 s 0.50 ● 0x0710 F07.17 Restoration time in retries after failure 0.01~30.00 s 10.00 ● 0x0711 F07.18 Options of retries after failure E08 * E0 7 * E02 E06 E05 E04 000000 O 0x0712 0: allow retry after 1: disable retry after failure failure F07.19 Action option 1 after failure E21 E 16 E1 5 E14 E13 E12 E08 E07 00000000 O 0x0713 1: stop according to stop 0: free stop mode