User Manual of EM760 High-Performance Inverter 326 F14.52 Stiffness coefficient of speed loop of motor 2 0~20 11 ● 0x0E34 F14.53 SVC zero- frequency processing 0: braking 1: not processed 2: seal the tube 2 O 0x0E35 F14.54 SVC zero- frequency braking current 50.0-400.0 (100.0 is the no-load current of the motor) % 100.0 O 0x0E36 F14.56 Voltage feedforward gain 0~100 % 0 ● 0x0E38 F14.57 Flux weakening control options 0: Invalid 1: direct calculation 2:
automatic adjustment 1 O 0x0E39 F14.58 Flux weakening voltage 70.00~100.00 % 100.00 ● 0x0E3A F14.59 Maximum field weakening current of synchronous motor 0.0-150.0 (100.0 is the rated current of the motor) % 100.0 ● 0x0E3B F14.60 Proportional gain of flux weakening regulator 0.00~60.00 0.50 ● 0x0E3C F14.61 Integral time offlux weakening regulator 0.000~6.000 s 0.200 ● 0x0E3D F14.62 MTPA control option of synchronous motor 0: Invalid 1:
valid 0 O 0x0E3E F14.63 Self-learning gain at initial position 0~200 % 100 O 0x0E3F F14.64 Frequency of low frequency band of injection current 0.00-100.00 (100.00 is the rated frequency of the motor) % 10.00 ● 0x0E40 F14.65 Injection current of low frequency band 0-200.0 (100.0 is the rated current of the motor) % 40.0 ● 0x0E41 F14.66 Regulator gain of low frequency band of injection current 0.00~10.00 0.50 ● 0x0E42 F14.67 Regulator integral time of low frequency band of injection current 0.00~300.00 ms 10.00 ● 0x0E43 F14.68 Frequency of high frequency band of injection current 0.00-100.00 (100.00 is the rated frequency of the motor) % 20.00 ● 0x0E44