sinee — Chapter 11 Function Code Table

User Manual of EM760 High-Performance Inverter 331 F15.33 Operating mode with set frequency less than lower frequency limit 0: running at the lower frequency limit 1: Shutdown 2: zero-speed running 0 O 0x0F21 F15.34 Fan control Ones place: Fan control mode 0: running after power-on 1: running at startup 2: intelligent operation, subject to temperature control Tens place: Electrification fan control 0: Run 1 minute first and then enter the fan control mode for running 1: Directly run in the fan control mode Hundreds place: Low-speed fan running mode enabled (above 200kW) 0: Low-speed running invalid 1:

Low-speed running valid 101 O 0x0F22 F15.35 Overmodulation intensity 1.00~1.10 1.05 ● 0x0F23 F15.36 Switching options of PWM modulation mode 0: invalid (7-segment PWM modulation) 1: valid (5-segment PWM modulation) 0 O 0x0F24 F15.37 Switching frequency of PWM modulation mode 0.00 to maximum frequency F00.16 Hz 15.00 ● 0x0F25 F15.38 Options of dead zone compensation mode 0: no compensation 1: compensation mode 1 2: compensation mode 2 1 O 0x0F26 F15.39 Terminal jog priority 0: Invalid 1: valid 0 O 0x0F27 F15.40 Deceleration time for quick stop 0.00~650.00(F15.13=0) 0.0~6500.0(F15.13=1) 0~65000(F15.13=2) s 1.00 ● 0x0F28 F15.41 Output power display coefficient 50.00~150.00 % 100.0 ● 0x0F29