4-2 Function Mode Acceleration/Deceleration Pattern This function is used when smooth acceleration/deceleration is needed. •Acceleration/deceleration pattern can be set according to each system. 4 Functions Operation Frequency Function This function makes calculations for two inputs and reflects the result as the output frequency. •Inputs FV and FI cannot be set simultaneously. Do not connect the signal lines for inputs FV and FI simultaneously. 4-23 Parameter No. Function name Data Default setting Unit A097 Acceleration pattern selection 00: Line 01: S-shape curve 00 A098 Deceleration pattern selection 00: Line 01: S-shape curve 00 Parameter No.
Set value 00 01 Line S shape A097 (Acceleration) frequency Output Time frequency Output Time A098 (Deceleration) frequency Output Time frequency Output Time Description Accelerates/Decelerates linearly before reaching the set output frequency value. Helps prevent the collapse of cargo on the elevating machine or conveyor. Parameter No. Function name Data Default setting Unit A141 Operation frequency Input A setting 00: Digital Operator (F001) 01: Digital Operator (FREQ adjuster) 02: Input FV 03: Input FI 04: RS485 communication 02 A142 Operation frequency Input B setting 03 A143 Operator selection 00: Addition (A + B) 01: Subtraction (A - B) 02:
Multiplication (A × B) 00 Related functions A001=10