omron — 2nd Control Function and Special 2nd Function

4-2 Function Mode „ Jogging Frequency •The Inverter may easily lead to a trip if the jogging frequency is set to high. Adjust A038 so that the Inverter does not trip. „ Jogging Stop Selection 4 •The deceleration time depends on the currently selected deceleration time in F003, F203, A093, or A293. When switching to normal operation, turn off the JG terminal after the deceleration time elapses, and enter the RUN command again. Note1: To perform the jogging operation, turn on the JG terminal before the FW or RV terminals. (Do the same if the RUN command source is set to the Digital Operator.) Functions JG FW Output frequency Jogging does not function if the FW signal is turned on first.

Note 2: If A039 is set to 02, data setting for the DC injection braking is required. 2nd Control Function and Special 2nd Function •This function is used to operate by switching two different types of motors. •By allocating 08 (SET) or 53 (SP-SET) to the desired multi-function input and then turning on/off the SET or SP-SET terminal, you can switch and control two different motors. •Switch to the 2nd control function at the SET terminal after turning off the RUN command and the Inverter output. •You can switch to the 2nd control function at the SP-SET terminal during operation.

4-44 39 = 01) JG FW RV Output frequency A038 Data Symbol Function name Status Description 08 SET 2nd control ON Enables the parameter for the 2nd motor. OFF Disables the parameter for the 2nd motor. 53 SP-SET Special 2nd function ON Enables the parameter for the special 2nd motor. OFF Disables the parameter for the special 2nd motor. Available input terminals C001, C002, C003, C004, C005