omron — Overload Warning

4-2 Function Mode „ Output Over Set Frequency (02: FA2) •Outputs a signal when the output frequency has exceeded the arrival frequencies during acceleration/deceleration set in [C042, C043 (FA2)]. C043 f on :1% of max. frequency f off :2% of max. frequency Output frequency C042 f on f off FA2 4 Overload Warning Functions If the load is too large, this function outputs an overload warning signal, allowing you to readjust the overload level to prevent a trip. This helps prevent mechanical damage due to an overload in the conveyors, or an operation line stop due to an overload trip of the Inverter.

Overload limit level b022 Overload warning level C041 Output current OL 4-55 Data Symbol Function name Status Description 03 OL Overload warning ON The Inverter output current has exceeded the C041 set value. OFF The Inverter output current has not reached the C041 set value. Available input terminals P1-PC, P2-PC, MA-MC (or MB-MC) Required settings C021, C026, C041 Parameter No. Function name Data Default setting Unit C041 Overload warning level 0.0: Does not operate. 0.1 to Rated current × 200%: Outputs OL signal when reaching the overload warning level. Rated current A