omron — Analog Output AM Terminal

4-2 Function Mode Analog Output AM Terminal •This function allows you to monitor the output frequency and current from the AM terminal on the control terminal block (terminal). •The AM terminal provides 0- to 10-V analog output. •For how to connect the AM terminal, refer to page 2-26. „ AM Selection •Select a signal to output from the following table. 4 Functions „ AM Adjustment •Adjust the calibration of the meter connected to the AM terminal by using the Inverter setting. (a) AM adjustment value change When b080 = 100 When C086 = 0.0 AM output AM output 10V 10V 5V 5V 0 1/2 FS Full scale (FS) Hz or A 0 1/2 FS Full scale (FS) Hz or A 4-62 Parameter No.

Function name Data Default setting Unit C028 AM selection 00: Output frequency 0 to 10 V (0 to Max. frequency (Hz)) 01: Output current 0 to 10 V (0% to 200% of the rated current) 00  Parameter No. Function name Data Default setting Unit b080 AM adjustment 0. to 255. (Adjust to the scale) 100.  C086 AM offset adjustment 0.0 to 10.0 (See the section below) 0.0 V b080 = 0 to 255 C086 = 0 to 10 Parall el shift