omron — Communication Function

4-2 Function Mode Query Response No. Field name Example (HEX) No. Field name Example (HEX) 1 Slave address *1 08 1 Slave address 08 3 Coil start number (MSB) 00 3 Number of data bytes 01 2 Function code 01 2 Function code 01 4 Coil start number (LSB) 07 4 Coil data *3 17 5 Number of coils (MSB) *2 00 5 CRC-16 (MSB) 12 6 Number of coils (LSB) *2 06 6 CRC-16 (LSB) 1A 7 CRC-16 (MSB) 0D 4 8 CRC-16 (LSB) 50 *1. Broadcasting cannot be performed. *2. When specifying the value for 0 or over 32 of the reading coils, the error code "03h" is replied. *3. Data is transferred by the number of data bytes. Functions The data received as the response shows the statuses of coils 7 to 14.

The data received here, "P7h = 00010111b", should be read with coil 7 as LSB, as follows: If the reading coil exceeds the defined coil range in the final coil data, such coil data is regarded as "0" and sent. Refer to " " (page 4-74) if the coil status reading command has not been performed normally. Reads the specified number of consecutive holding register contents from the specified holding reg- ister addresses. (Example) Read the factors on the past three trips from the Inverter with slave address 5. Below are the data on past three trips: 4-70 Coil No.