omron — Monitor Mode (dooo) / Basic Function Mode (Fooo)

Appendix-1 Parameter List AppAppendix Appendix-1 Parameter List Monitor Mode (d ††† ) / Basic Function Mode (F ††† ) Appendix * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. App-1 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value d001 Output frequency monitor 0.0 to 400.0   Hz d002 Output current monitor 0.0 to 999.9   A d003 Rotation direction monitor F: Forward o: Stop r: Reverse    d004 PID feedback value monitor 0.00 to 99.99 100.0 to 999.9 1000. to 9999.    d005 Multi-function input monitor Example) ON Terminal OFF S2, S1:

ON S6 S5 S4 S3 S2 S1 Terminal S6, S5, S4, S3: OFF    d006 Multi-function output monitor Example) ON Terminal OFF P1, P2: ON MA P2 P1 Terminal MA: OFF    d007 Output frequency monitor (after conversion) 0.00 to 99.99 100.0 to 999.9 1000. to 9999. 1000 to 3996 (10000 to 39960) (Output frequency × Conversion factor of b086)    d013 Output voltage monitor 0. to 600.   V d016 Total RUN time 0. to 9999. 1000 to 9999 100 to 999[h]   h d017 Power ON time monitor 0. to 9999. 1000 to 9999 100 to 999[h]   h d080 Fault frequency monitor 0. to 9999.

   d081 Fault monitor 1 (Latest) Error code (condition of occurrence) → Output frequency [Hz] → Output current [A] → Internal DC voltage [V] → RUN time [h] → ON time [h]   d082 Fault monitor 2 d083 Fault monitor 3