omron — Extended Function Mode

Appendix-1 Parameter List Appendix * 2nd control is displayed when '08 (2nd control)' is allocated to one of multi-function inputs from C001 to C006. App-6 Parameter No. Function name Monitor or data range (Digital Operator) Default setting Changes during operation Unit Set value DC injection braking A051 DC injection braking selection 00: Disabled 01: Enabled 00 No  A052 DC injection braking frequency 0.0 to 60.0 0.5 No Hz A053 DC injection braking delay time 0.0 to 5.0 0.0 No s A054 DC injection braking power 0. to 100. 50. No % A055 DC injection braking time 0.0 to 60.0 0.5 No s A056 DC injection braking method selection 00: Edge operation 01:

Level operation 01 No  Upper/Lower limit, Jump A061 Frequency upper limit 0.0/Frequency lower limit to Max. frequency 0.0 No Hz A261 *2nd frequency upper limit 0.0/Frequency lower limit to 2nd Max. frequency 0.0 A062 Frequency lower limit 0.0/Starting frequency to Frequency upper limit 0.0 No Hz A262 *2nd frequency lower limit 0.0/Starting frequency to 2nd frequency upper limit 0.0 A063 Jump frequency 1 Jump frequency: 0.0 to 400.0 Jump frequency width: 0.0 to 10.0 0.0 No Hz A064 Jump frequency width 1 0.5 A065 Jump frequency 2 0.0 A066 Jump frequency width 2 0.5 A067 Jump frequency 3 0.0 A068 Jump frequency width 3 0.5